Servo Drive Overvoltage Fault on Deceleration: Causes and Fixes

A servo drive that faults on overvoltage during deceleration is reporting that energy returned by the load has nowhere to go. When the motor slows, it acts as a generator. The drive’s four-quadrant power stage passes that energy back onto the DC bus, the bus capacitors charge, and once bus voltage crosses the drive’s overvoltage limit, the drive shuts its output off.

In most systems the fix is a shunt regulator sized for the worst-case deceleration. The rest of the time, the cause is a supply voltage set too close to the limit, a shunt that is misconfigured or undersized, or a deceleration rate that returns energy faster than the shunt circuit can absorb it. This guide shows how to confirm which one you have, how to calculate the energy involved, and how to choose a fix.

Why Deceleration Raises Bus Voltage

During acceleration, current flows from the supply through the drive into the motor. During deceleration, the drive applies torque against the direction of motion, and the motor converts the load’s kinetic energy back into electrical energy. The motor windings and the drive’s power stage dissipate part of it as heat. The remainder flows onto the DC bus.

The bus has two places to put that energy: the bus capacitance, or a supply that can accept reverse current. Most DC supplies used with servo drives cannot accept it. An unregulated transformer-rectifier supply blocks reverse current at its rectifier, and most switch-mode supplies are not designed to sink current. That leaves the capacitance, which stores very little energy within the available voltage margin:

Ecap = ½ · C · (VOV2 − Vbus2)

Ecap = energy the bus capacitance can absorb, J. C = total bus capacitance, F. VOV = drive overvoltage limit, V. Vbus = bus voltage before deceleration, V.

A DigiFlex® Performance™ DPRALTE-020B080 has 33 µF of internal bus capacitance and a DC bus overvoltage limit of 88.3 VDC. On a 48 VDC bus, that capacitance absorbs about 0.09 J before the bus reaches the limit. A small axis stopping from a few thousand rpm returns tens of joules, so the bus crosses the limit within the first milliseconds of the stop.

What Happens When the Drive Trips

At the overvoltage shutdown point, the drive disables its output, and output current and braking both stop. Energy stored in the motor inductance continues to flow through the power stage diodes and charges the bus further, so the peak you measure can sit above the trip threshold itself.

Safety: once braking stops, the load coasts. A horizontal axis runs on until friction or a hard stop halts it. A vertical axis or any overhauling load accelerates under gravity unless a holding brake engages. Treat repeated overvoltage faults on a vertical axis as a safety issue, and confirm that the brake engages on any drive fault, not only on a commanded disable.

Common Causes

The causes below are listed from most to least likely in a typical DC-bus servo system. The fault signature usually points to one of them before any calculation.

Cause Typical signature First check
No path for regenerative energy Trips at the end of fast moves or on quick stops, never at constant speed Is a shunt regulator fitted? Can the supply sink current?
Supply voltage too close to the overvoltage limit Trips even on gentle stops, or only at certain sites or times of day Bus voltage at idle versus the overvoltage limit
Shunt regulator misconfigured or undersized Shunt fitted but the bus still reaches the trip point, or the shunt runs hot Turn-on voltage, enable setting, wiring and fuse, dissipation rating
Overhauling or vertical load Trips while lowering a load, even at modest speed Potential energy per downward move
Deceleration faster than the shunt circuit can absorb Trips on emergency or quick-stop ramps but not on normal stops Quick-stop deceleration rate in the controller and drive
Several axes stopping together on one bus Trips only when axes decelerate at the same time Motion sequence and total energy on the shared bus

No path for regenerative energy

This is the default state of an axis on an unregulated supply with no shunt regulator. Nothing on the bus can absorb more than the capacitance holds, so any stop that returns more energy than the calculation above allows will trip the drive.

Supply voltage too close to the limit

AMC’s hardware installation guidance calls for the nominal supply voltage to sit at least 10% below the lower of two values: the drive overvoltage limit and the shunt regulator turn-on voltage. An unregulated supply’s output tracks its AC input, so a line running 10% high raises the bus 10% before any regeneration occurs. Check this case first when faults appear on one site or shift but not another.

Shunt regulator misconfigured or undersized

A shunt with a turn-on voltage above the drive’s overvoltage limit never acts. A turn-on voltage too close to the supply voltage makes the shunt conduct during normal operation and overheat. A dissipation rating below the average regenerative power overheats the shunt resistor during continuous cycling. On AC-input DigiFlex Performance DPR drives, the internal shunt regulator has to be enabled and configured in DriveWare® before it operates, and models without an internal shunt resistor need an external one connected.

Overhauling and vertical loads

Lowering a mass converts potential energy to electrical energy for the whole downward move, not only at the end of it. A 20 kg load lowered 0.5 m returns 98 J on top of its kinetic energy, which is twice what the worked example below produces from a full-speed stop.

Deceleration rate and tuning

Energy per stop depends on speed and inertia, not on how quickly the axis stops. Peak regenerative power does depend on the stop time, because the same energy arrives in less time. A shunt that keeps up with a 200 ms stop can fall behind on a 50 ms quick stop. A poorly damped velocity loop that overshoots and reverses torque at the end of a move adds regenerative pulses on top of the profile’s nominal energy.

Shared buses and batteries

On a shared bus, the energies of axes that decelerate together add. On a battery-powered machine such as an AMR, the battery absorbs regenerative energy only while its battery management system accepts charge current. A fully charged pack, or a BMS that opens its charge path, leaves the bus with the same problem as an unregulated supply.

How to Diagnose the Fault

Before you start: bus capacitors hold charge after power is removed. Follow lockout/tagout, allow time for the bus to discharge fully, and confirm bus voltage with a meter before touching terminals. Do not turn the motor shaft by hand with power off. The motor acts as a generator and charges the bus through the drive.

  1. Read the fault history. In DriveWare, open the Drive Status window and review active and history events. On FlexPro® drives, check the equivalent fault record in ACE. Confirm that the event is overvoltage and note where in the motion cycle it occurs. Expected result: the fault coincides with a deceleration segment or a downward move.
  2. Measure bus voltage at idle. Enable the drive and hold position with no motion. Measure between the DC power input and power ground at the drive terminals. Expected result: at least 10% below the lower of the overvoltage limit and the shunt turn-on voltage. If it is higher, the problem is supply voltage or line voltage, not regeneration.
  3. Scope the bus during the worst-case stop. Probe the same terminals, using a differential probe if the bus is not referenced to earth, and trigger on a rising edge about 10% above nominal bus voltage. Run the move that faults. Expected result: a rise that peaks below the shunt turn-on voltage, or flattens at it when a shunt is fitted. A trace that climbs straight to the trip point means the energy has no path.
  4. Confirm the shunt switches. With an external shunt regulator, the scope trace from step 3 shows it: the bus flattens at the clamp voltage. On DigiFlex Performance DPR drives with an internal shunt regulator, the Power LED also flashes red while the drive is shunting energy. If the bus climbs past the expected clamp level and the shunt never switches, check its turn-on voltage, wiring, fuse and, on drives with an internal shunt regulator, its enable setting in DriveWare. Expected result: the shunt switches during deceleration and the bus stops rising.
  5. Halve the deceleration rate as a test. Expected result: if the fault clears, regeneration is confirmed as the cause. Keep the slower rate only if the machine’s cycle time allows it. Otherwise it is a diagnostic step, not a fix.
  6. Calculate the energy. Use the method below and compare the result with the capacitance and the shunt rating. Expected result: the numbers explain the scope trace. If they do not, recheck inertia and speed values against the real machine.

How to Calculate Regenerative Energy

Two terms cover nearly every application: kinetic energy released by slowing down and potential energy released by lowering a load:

Ekin = ½ · J · (ω12 − ω22)

J = total inertia reflected to the motor shaft, kg·m². ω1, ω2 = motor speed before and after deceleration, rad/s.

Epot = m · g · h

m = moving mass, kg. g = 9.81 m/s². h = height lowered during the move, m.

Pavg = Estop / tcycle, Ppeak = Tdec · ω1

Estop = energy returned per cycle, J. tcycle = cycle time, s. Tdec = deceleration torque, N·m.

These values are upper bounds. Winding resistance and power stage losses absorb part of the energy, so the full figures carry a built-in margin.

Worked example

A single axis runs a DPRALTE-020B080 from a 48 VDC unregulated supply. The motor has a torque constant of 0.1 N·m/A, total reflected inertia is 1.0 × 10−3 kg·m², and the axis stops from 3,000 rpm, or 314.2 rad/s, to rest in 200 ms once per 1 s cycle.

  • Energy per stop: 0.5 × 1.0 × 10−3 × 314.2² = 49.3 J.
  • Deceleration torque and current: 1.0 × 10−3 kg·m² × 1,571 rad/s² = 1.57 N·m, or 15.7 A, inside the drive’s 20 A peak rating.
  • Power: 1.57 N·m × 314.2 rad/s = 493 W at the start of the stop, 247 W averaged over the 200 ms stop, and 49 W averaged over the 1 s cycle.
  • Capacitance alone: the drive’s 33 µF absorbs 0.09 J. Holding 49.3 J between 48 V and 88.3 V would take about 18,000 µF. A 4,700 µF capacitor added on its own would let the bus head toward 152 V.

The capacitance route is impractical here, so the fix is a shunt regulator. Its turn-on voltage has to sit below the drive’s 88.3 V limit, and the supply’s high-line output of 52.8 V has to sit at least 10% below the turn-on voltage. That puts the turn-on voltage between 58.7 V and 88.3 V. An AMC SRST70 meets both conditions with a 70 V clamp, and its 95 W rated dissipation covers the 49 W average with margin. At a 70 V clamp, the 493 W peak corresponds to about 7 A through the shunt, so check that figure against the SRST70 datasheet’s resistor value.

Fixes and Their Tradeoffs

Fix When it fits Tradeoff
External shunt regulator Unregulated supply with repeated stops or vertical moves Adds a component and heat to manage. Size for average power and check peak current
Internal shunt regulator with external resistor Drives that include an internal regulator, such as AC-input DigiFlex Performance DPR models Must be enabled in DriveWare. Resistor must meet the datasheet minimum resistance
Added bus capacitance Small energies, such as occasional stops of low-inertia axes Stores energy for reuse, but the size needed grows fast and increases inrush current at power-up
Regulated supply with built-in shunt Multi-axis machines, shared buses, wide line variation Higher cost and complexity than an unregulated supply
Lower top speed Cycle time has margin Energy scales with speed squared. A 10% speed cut removes 19% of the energy per stop
Longer deceleration The safety function allows a longer quick-stop ramp Reduces peak power, not energy per stop
Lower supply voltage Back-EMF headroom at top speed allows it More margin to the trip point, less top speed
Staggered deceleration Shared-bus machines with a flexible motion sequence Requires controller changes and can lengthen the cycle

After any fix, repeat steps 3 and 4 of the diagnostic procedure. The bus should rise to the shunt clamp level and flatten well below the overvoltage limit, and the shunt’s case temperature should stabilize during continuous operation at the worst-case cycle rate.

Matching AMC Hardware to the Fix

DigiFlex Performance DC-input drives such as the DPRALTE-020B080 operate as four-quadrant regenerative drives with hardware overvoltage and undervoltage protection. Overvoltage limits depend on the voltage class and the part number: the DPRALTE-020B080 trips at 88.3 VDC, and the 200 V-class DPRALTE-025B200 trips at 198 VDC. Check the datasheet for your part number before setting a shunt turn-on voltage.

The SRST series covers standard clamp voltages of 50, 70, 80, 90, 175, 185, 380 and 400 VDC, and the SRST50 through SRST185 are designed for drives up to 200 V. The SRST70 and SRST80 are each rated for 95 W of dissipation. For multi-axis or high-regeneration systems, the PFC2400W375 regulated supply includes a built-in shunt regulator and power factor correction. Supply sizing, including back-EMF headroom and the regenerative energy budget, is covered step by step in How to Size a Power Supply for a Servo Drive.

Key Takeaways

  • An overvoltage fault on deceleration means returned energy exceeded what the bus can hold. Drive capacitance alone absorbs a fraction of a joule on small drives.
  • Measure bus voltage at idle before blaming regeneration. A supply within 10% of the trip point faults on gentle stops.
  • Scope the bus during the worst-case stop. A trace that climbs straight to the trip point means the energy has no path.
  • Size the shunt regulator for average power over the cycle and check peak current. Set its turn-on voltage below the drive’s overvoltage limit and high enough that the supply’s high-line output sits at least 10% below it.
  • On vertical axes, an overvoltage trip removes braking. Confirm the holding brake engages on any drive fault.
Designing motion into something?

Brushed and brushless. Analogue through EtherCAT.

A-M-C FlexPro servo drive
FlexPro
A-M-C DigiFlex Performance servo drive
DigiFlex Performance
A-M-C AxCent servo drive
AxCent

Designing motion into something?
Talk it through with a support engineer. Not a sales call.

Weekdays 8 to 5 Pacific. A support engineer, not a sales rep.

Designed & built in Camarillo, CA

Blog

Recent Posts

Registration Required

I accept that logging in will place cookies on my browser

* If you do not already have a registered account, additional information may be required.

Thank You For Requesting Access

To view the requested file, please click the button below.

Begin Download